Output reactors
Three phase reactors for frequency converters are designed for 3x400V/230V, 50Hz power system. Reactors are manufactured with IP00 protection degree, insulation class „F“ for ambient temperature of 40°C. Relevant standard is EN 61 558-2-20. Wide current range covers reactors from 6 to 630 A.
Output reactors are connected between the converter and supplied drives. They decrease converter overloading by reduction of the capacitive current generated by long incoming drives cables. It is recommended to place reactors close to the converters to avoid voltage disturbing radiation of the converter.
Output reactors
Type | PDF | Rated current IN [A] | Inductance LN [mH] | Losses Pmax [W] |
TMA 1-6 |
-
| 6 | 2,50 | 10,1 |
TMA 1-10 |
-
| 10 | 1,50 | 14,0 |
TMA 1-16 |
-
| 16 | 0,90 | 19,6 |
TMA 1-25 |
-
| 25 | 0,60 | 29,4 |
TMA 1-32 |
-
| 32 | 0,50 | 38,0 |
TMA 1-40 |
-
| 40 | 0,37 | 40,0 |
TMA 1-63 |
-
| 63 | 0,23 | 55,0 |
TMA 1-100 |
-
| 100 | 0,15 | 76,0 |
TMA 1-160 |
-
| 160 | 0,09 | 112,0 |
TMA 1-230 |
-
| 230 | 0,06 | 140,0 |
TMA 1-320 |
-
| 320 | 0,05 | 185,0 |
TMA 1-400 |
-
| 400 | 0,04 | 214,0 |
TMA 1-630 |
-
| 630 | 0,025 | 303,0 |